Skip to main content
Siemens 5SY4105-7KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4105-7KK11 SENTRON MCB, 1P C 0.5A, 10kA EN 60898

MPN5SY4105-7KK11

Siemens SENTRON 5SY4105-7KK11, 1-pole miniature circuit breaker, C characteristic, 0.5 A rated current, 10 kA breaking capacity per EN 60898, 35 kA per IEC 60947-2, 1 MW width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4105-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY4105-7KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SY4105-7KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4105-7KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

DIN-rail fit and thermal derating

Occupies 1 modular width unit (18 mm wide, 90 mm tall, 76 mm deep), with an installation depth of 70 mm behind the panel surface. Mount in any position. Rated 0.5 A at 35 °C ambient, but derates to 0.47 A at 40 °C, 0.45 A at 45 °C, 0.44 A at 50 °C, 0.42 A at 55 °C, and 0.4 A at 60 °C (–). If your panel runs warm — common in sealed railway enclosures — size the load to the derated figure, not the 35 °C number.

Halogen-free and silicon-free. Sealable for lockout/tagout. Energy limitation class 3. The brand provides standard compliance documentation including RoHS and REACH declarations; the part is designed to meet UL and IEC standards as per its EN 60898 and IEC 60947-2 ratings.

Frequently asked questions

How do I get current pricing and availability for 5SY4105-7KK11?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and pricing are confirmed at quote time.

Will 5SY4105-7KK11 drop into a panel specified around 5SY4101-7CV without rewiring?

Both are 1-pole SENTRON MCBs with the same 18 mm width and DIN-rail mounting. The 5SY4105-7KK11 is a 0.5 A C-curve; the 5SY4101-7CV is a different rating. If the panel wiring and load match 0.5 A, it fits mechanically without rewiring.

What is 5SY4105-7KK11's listed depth (76 mm) on this component line?

The depth is 76 mm, with an installation depth of 70 mm.

What is 5SY4105-7KK11's listed width (18 mm) on this component line?

The width is 18 mm, which is 1 modular width unit.

What compliance documentation does this brand provide for 5SY4105-7KK11 (RoHS, REACH, UL, IEC)?

The part is halogen-free and silicon-free. Standard RoHS and REACH declarations are available from the brand. The breaking capacity is certified per EN 60898 at 10 kA and per IEC 60947-2 at 35 kA.

MPN
5SY4105-7KK11