Mounting & Integration
The IP20 rating applies only with connected conductors — the breaker body itself is finger-safe but not sealed against dust ingress when the terminals are open.
Environmental & Compliance
Rated for ambient temperatures from -40 °C to 75 °C, with a derating curve for continuous load above 55 °C (95 % humidity at 55 °C, 55 % at 70 °C, 35 % at 75 °C). Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — this is the spec that qualifies it for onboard rail and shipboard panels where constant vibration is present.