Skip to main content
Siemens 5SY4106-7KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4106-7KK11 SENTRON MCB, 1P C-Curve 6A, 10kA

MPN5SY4106-7KK11

Siemens SENTRON 5SY4106-7KK11, 1-pole miniature circuit breaker, C characteristic, 6 A rated current, 10 kA breaking capacity per EN 60898-1, 35 kA per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4106-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4106-7KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY4106-7KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4106-7KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The C-curve (characteristic C) means the magnetic trip operates at 5 to 10 times rated current — so for a 6 A breaker, instantaneous trip occurs between 30 A and 60 A. It's not the D-curve you'd grab for high-inrush motor starts, nor the B-curve for sensitive electronic loads. Temperature derating is built into the spec: at 40 °C ambient the breaker is rated 5.63 A, at 50 °C it drops to 5.24 A, and at 60 °C it's 4.82 A. The 18 mm width (1 modular unit) snaps onto standard DIN rail.

Designed for railway and industrial environments

Overvoltage category III suits fixed installations and distribution panels. Energy limitation class 3 means it limits the let-through energy (I²t) during a fault — less stress on downstream wiring and equipment. The sealable feature (yes) lets you lock the toggle in position to prevent unauthorized reset, which is useful in safety-critical or shared-access panels.

Frequently asked questions

Where can I buy 5SY4106-7KK11 and get a price?

This part is sourced and quoted to order through our independent distribution channel. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SY4106-7KK11?

It's rated 10 kA per DIN EN60898-1 and 35 kA per IEC 60947-2. The 35 kA figure is the one to use for industrial panel coordination.

Does 5SY4106-7KK11 drop into a panel specified for 5SY4106-7CV without rewiring?

Both are 1-pole SENTRON MCBs with the same 18 mm width, C-curve, and 6 A rating, so the mechanical fit and basic protection are the same. The 5SY4106-7KK11 carries a railway-application designation and a higher IEC 60947-2 breaking capacity (35 kA vs the 7CV's typical 10 kA), so verify the fault-current rating your panel requires before swapping — the 7KK11 may be over-specified or exactly right depending on the installation.

What compliance documentation is available for 5SY4106-7KK11?

The breaker is certified to DIN EN60898-1 and IEC 60947-2. It's halogen-free and silicon-free. Standard documentation includes the manufacturer's declaration of conformity; specific RoHS/REACH declarations are available on request through the RFQ process.

MPN
5SY4106-7KK11