Skip to main content
Siemens 5SY4108-7CC11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4108-7CC11 SENTRON MCB, 1P C-curve 8A 10kA

MPN5SY4108-7CC11

Siemens SENTRON 5SY4108-7CC11, 1-pole miniature circuit breaker, C-curve 8 A, 10 kA breaking capacity per EN 60898, 400 V AC, 72 V DC max, 1 width unit (18 mm).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4108-7CC11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY4108-7CC11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Overvoltage categoryIII
5SY4108-7CC11 — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SY4108-7CC11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

Designed for railway applications and mechanical engineering / industry, this breaker carries an overvoltage category III rating, meaning it is suitable for fixed-installation panels where transient overvoltages from the mains supply are expected.

Terminal capacity and wiring constraints

The screw-type terminals accept solid or stranded conductors from 0.75 mm² up to 35 mm², with a tightening torque range of 2.5 to 3.5 N·m. Combined terminals at both top and bottom allow daisy-chaining or feed-through wiring without separate busbar connectors. The breaker is sealable for anti-tamper applications, and touch protection is built in — no exposed live parts when conductors are properly terminated. Ambient temperature range is -40 to +70 °C, storage -40 to +75 °C, with humidity derating: max 95% at 55 °C, 55% at 70 °C, 35% at 75 °C.

Material and compliance profile

Halogen-free and silicon-free construction reduces corrosive off-gassing in enclosed panels — relevant for food-and-bev or marine environments where outgassing can damage contacts. The breaker is classified as energy limiting class 3, meaning it limits let-through energy in a fault, reducing stress on downstream components. No neutral conductor switching — this is a line-only 1P device.

Frequently asked questions

Who supplies 5SY4108-7CC11 and how is it quoted for volume purchases?

This part is sourced to order against an RFQ through independent distribution. Submit a request with your target quantity and delivery window; availability and current pricing are confirmed at quote time.

What is 5SY4108-7CC11's rated breaking capacity?

10 kA per EN 60898 at 400 V AC. This is the standard breaking capacity for final-distribution MCBs in residential and light commercial panels.

What conductor sizes does the 5SY4108-7CC11 accept?

Solid or stranded conductors from 0.75 mm² up to 35 mm². The screw terminals require a tightening torque of 2.5 to 3.5 N·m.

What compliance documentation does this brand provide for 5SY4108-7CC11?

The breaker is halogen-free and silicon-free, and carries IP20 protection with connected conductors. Standard Siemens SENTRON documentation includes CE declaration and manufacturer declarations for RoHS/REACH compliance upon request.

MPN
5SY4108-7CC11