Breaking capacity and standards coverage
Rated 10 kA according to EN 60898-1 and 20 kA according to IEC 60947-2 at 400 V AC. That IEC 60947-2 figure gives headroom for industrial fault levels where the lower EN rating would be marginal. For DC circuits, it carries 15 kA at 60 V DC (max 72 V DC) per IEC 60947-2. Under UL 1077 and CSA C22.2 No. 235, it is rated 5 kA.
Rated for ambient temperatures from -40 °C to 75 °C, with derating above 55 °C per the humidity curve (max 95% RH at 55 °C, tapering to 35% at 75 °C). Mounting position is any; the quick-assembly system clips onto a DIN rail. Sealable terminals (top and bottom combined) allow tamper-proofing in metering or critical circuits.