Siemens 5SY4108-8CC — 1-Pole MCB (DIN Rail)

Siemens 5SY4108-8CC SENTRON MCB, 1P D-curve 8A, 10kA

MPN5SY4108-8CC

Siemens SENTRON 5SY4108-8CC, 1-pole miniature circuit breaker, D characteristic, 8 A (40 °C), 10 kA per EN 60898, 1 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4108-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4108-8CC — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage categoryIII
5SY4108-8CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4108-8CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY4108-8CC is a 1-pole miniature circuit breaker from the SENTRON 5SY series, sized at 1 modular width unit (18 mm) for DIN-rail mounting in distribution boards and control panels. Its D tripping characteristic means it tolerates the high inrush currents of motor and transformer loads — the magnetic trip threshold sits between 10× and 20× rated current, so it won't nuisance-trip on a motor start but clears hard faults fast. Rated 8 A at 40 °C ambient, the breaker delivers 10 kA breaking capacity per EN 60898 (5 kA per UL 1077 / CSA C22.2 No.235), which covers most industrial and commercial panel fault levels. The 1-pole design switches the line conductor only — no neutral pole — so it's intended for single-phase branch circuits or as a phase leg in multi-pole assemblies.

Temperature derating — the real current rating

The 8 A rating holds only up to 35 °C. Above that, the breaker must be derated: 7.35 A at 40 °C, 7 A at 45 °C, 6.63 A at 50 °C, and 6.25 A at 55 °C. If your panel runs warm — say 50 °C inside the enclosure — the usable continuous current drops to 6.63 A. Plan the branch circuit load against the derated value at your actual ambient, not the 35 °C sticker figure.

IP20 with connected conductors — standard for panel-internal use.

Frequently asked questions

What is the breaking capacity of 5SY4108-8CC?

10 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No.235, both at AC voltage.

What is the temperature derating for 5SY4108-8CC?

Rated 8 A at 35 °C, derated to 7.35 A at 40 °C, 7 A at 45 °C, 6.63 A at 50 °C, and 6.25 A at 55 °C.

Where can I buy 5SY4108-8CC?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.