Siemens 5SY4108-8CC11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4108-8CC11 SENTRON MCB, 1P D 8A, 10kA

MPN5SY4108-8CC11

Siemens SENTRON 5SY4108-8CC11, 1-pole miniature circuit breaker, D tripping characteristic, 8 A rated current, 10 kA breaking capacity per EN 60898, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4108-8CC11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4108-8CC11 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage categoryIII
5SY4108-8CC11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4108-8CC11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens SENTRON 5SY4108-8CC11 — D-curve 8 A MCB for high-inrush loads

The Siemens SENTRON 5SY4108-8CC11 is a 1-pole miniature circuit breaker with a D tripping characteristic, rated 8 A at AC and a 10 kA breaking capacity per EN 60898. It's designed for railway applications and carries IP20 protection with connected conductors.

The 8 A rating at 35 °C derates to 7.35 A at 40 °C, 7 A at 45 °C, 6.63 A at 50 °C, 6.25 A at 55 °C, and 5.83 A at 60 °C. If the panel ambient runs at 50 °C, the breaker is good for about 6.6 A continuous — size the load accordingly.

Mounting position any. Combined terminals top and bottom — wire both sides without removing the busbar. Touch protection built in. Sealable for tamper-evident installations. Halogen-free and silicon-free for environments sensitive to outgassing.

Frequently asked questions

What is the breaking capacity of 5SY4108-8CC11?

10 kA rated breaking capacity per EN 60898. This is the maximum prospective fault current it can safely interrupt at the rated voltage.

What does the D tripping characteristic mean for this breaker?

The D curve has a magnetic trip threshold of 10–20× rated current (80–160 A for this 8 A unit). It's designed for circuits with high inrush — motor starters, transformers, power supplies — where a B or C curve would nuisance-trip on start-up.

What are the temperature derating values for 5SY4108-8CC11?

Rated 8 A at 35 °C, derated to 7.35 A at 40 °C, 7 A at 45 °C, 6.63 A at 50 °C, 6.25 A at 55 °C, and 5.83 A at 60 °C.

Where can I buy 5SY4108-8CC11 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm quote.