Skip to main content
Siemens 5SY4110-8 — 1-Pole MCB (DIN Rail)

Siemens 5SY4110-8 SENTRON MCB, 1P, D-Curve, 10 kA

MPN5SY4110-8
Active

Siemens SENTRON 5SY4110-8, 1-pole miniature circuit breaker, D tripping characteristic, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, 400 V AC, 18 mm wide.

$15.07Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4110-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4110-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY4110-8 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4110-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

What the ratings mean for fit

The Siemens 5SY4110-8 is a 1-pole SENTRON miniature circuit breaker with a D tripping characteristic. The D-curve means it tolerates high inrush currents — typically 10 to 20 times the rated current — making it the right choice for motor circuits, transformers, and other inductive loads where the start-up surge would nuisance-trip a B- or C-curve breaker. The 10 kA breaking capacity per EN 60898-1 covers standard residential and light commercial fault levels; the 20 kA rating per IEC 60947-2 gives headroom for industrial panel applications where higher prospective fault currents are expected. For DC circuits, it's rated 15 kA at up to 72 V, so it handles battery-backed control circuits and DC bus protection in the same footprint. The 18 mm width (1 modular unit) snaps onto a standard DIN rail, and the 'any' mounting position means you can orient it vertically or horizontally inside the enclosure without derating — useful when panel space forces unconventional layouts. The IP20 rating with connected conductors is typical for enclosed panel mount; it's not intended for washdown environments.

Where it fits in the panel

The 5SY4110-8 is a SENTRON series device, designed for quick assembly on DIN rail with a combined top and bottom terminal that accepts both busbar and wire — no need for separate feed-through terminals. The 70 mm installation depth leaves room behind the gland plate for wiring. Sealable with a lead seal if the application requires tamper evidence. Halogen-free and silicon-free construction matters for environments where outgassing could contaminate sensitive equipment or coatings.

Environmental and compliance

Rated for ambient temperatures from -40 °C to 75 °C, with humidity derating above 55 °C: max 95% RH at 55 °C, tapering to 35% at 75 °C. That covers most industrial enclosures including unheated warehouses and outdoor cabinets. Vibration resistance per IEC 60068-2-6 (±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz) means it holds up on machinery-mounted panels near conveyors or compressors. The overvoltage category III and pollution degree 3 ratings confirm it's suitable for fixed installations in industrial environments where transient overvoltages are common.

Frequently asked questions

Where can I buy 5SY4110-8 and how do I get a price?

Sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability confirmation.

Will 5SY4110-8 drop into a panel specified around 5SY4140-7 without rewiring?

Both are 1-pole SENTRON MCBs on the same 18 mm DIN-rail footprint with combined terminals, so the mechanical swap is straightforward. The key difference is the tripping characteristic: 5SY4110-8 is D-curve (high inrush), while 5SY4140-7 is a different curve — verify the existing branch's load type before substituting.

What compliance documentation does this brand provide for 5SY4110-8?

The breaker is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235. Halogen-free and silicon-free construction is declared. Standard Siemens SENTRON documentation includes the Declaration of Conformity and the UL/CSA file number.

MPN
5SY4110-8