At DC per IEC 60947-2 it's rated 15 kA up to 72 V, so it also works in DC sub-distribution for control cabinets or solar combiner boxes. Mounting position is unrestricted, and the combined top/bottom terminals accept feed from either direction — no need to reorient the breaker for top-feed vs bottom-feed panels.
The 5SY4113-6 carries approvals to IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 / CSA C22.2 No. 235 — the UL 1077 rating is 5 kA, which is the relevant figure for North American supplementary protection applications.
Deployment context and environmental limits
Rated for ambient temperatures from -40 °C to 75 °C, with humidity derating above 55 °C (max 95% RH at 55 °C, tapering to 35% at 75 °C).