Skip to main content
Siemens 5SY4113-6KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4113-6KK11 SENTRON MCB, 1P B 13A 10kA

MPN5SY4113-6KK11

Siemens SENTRON miniature circuit breaker, 5SY4113-6KK11, 1-pole B-curve 13 A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 400 V AC, 72 V DC max, railway-rated, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4113-6KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY4113-6KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)10 kA
Overvoltage categoryIII
5SY4113-6KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4113-6KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY4113-6KK11 is a 1-pole SENTRON miniature circuit breaker rated 13 A with a B tripping characteristic, designed for 400 V AC and up to 72 V DC maximum.

The 13 A rating covers branch circuits up to that continuous load; the 10 kA (EN 60898) breaking capacity is the standard for domestic and light commercial distribution boards, while the 20 kA (IEC 60947-2) rating lets it handle higher fault levels in industrial panels without cascading upstream.

Deployment context

This MCB is rated for railway applications and mechanical engineering / industry, meaning it's built for vibration, temperature swings (-40 °C to +75 °C), and high humidity environments. Halogen-free and silicon-free construction matters in rail and tunnel installations where smoke toxicity and silicone contamination are concerns.

Frequently asked questions

What is the breaking capacity of 5SY4113-6KK11?

It breaks 10 kA per EN 60898 and 20 kA per IEC 60947-2 at 400 V AC, and 15 kA at DC per IEC 60947-2. For UL 1077 / CSA C22.2 No. 235 it is rated 5 kA.

Will 5SY4113-6KK11 drop into a panel specified around 5SY3132-6?

Both are 1-pole SENTRON MCBs on the same 18 mm width unit with quick-assembly mounting, so the physical footprint and rail clip are identical. The difference is the rating: 5SY4113-6KK11 is 13 A B-curve; 5SY3132-6 is a different current/curve combination. Check the BOM rating before swapping.

Where can I buy 5SY4113-6KK11?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — confirmed at quote time.

MPN
5SY4113-6KK11