It carries a 10 kA breaking capacity under EN 60898 and a 35 kA rating under IEC 60947-2, which means it can safely interrupt fault currents up to those levels without welding or cascading failure upstream — the 35 kA figure is the one that matters for industrial panel coordination with high available fault current. This breaker is explicitly listed for railway applications and mechanical engineering/industry operation, so it's built for the vibration, temperature swings, and dirt you find in traction power or factory-floor distribution. The 1-module-wide (18 mm) footprint fits standard DIN-rail enclosures, and the quick-assembly fastening method speeds up rail mounting.
Temperature derating and real-world current
The 1.6 A rating is at 35 °C ambient. At 40 °C it derates to 1.52 A, at 50 °C to 1.44 A, and at 60 °C to 1.36 A (–).
Panel fit and mounting details
Width is 18 mm (1 modular unit), depth 76 mm, height 90 mm. Installation depth is 70 mm, which matters when routing conductors behind the DIN rail. The enclosure is sealable for tamper-proofing after commissioning. Touch protection is built in.