Skip to main content
Siemens 5SY4116-6-ZW07 — 1-Pole MCB (DIN Rail)

Siemens 5SY4116-6-ZW07 SENTRON MCB, 1P, B-Curve, 10 kA

MPN5SY4116-6-ZW07
Active

Siemens SENTRON 5SY4116-6-ZW07, 1-pole miniature circuit breaker, B characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4116-6-ZW07 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4116-6-ZW07 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SY4116-6-ZW07 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4116-6-ZW07 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY4116-6-ZW07 is a 1-pole miniature circuit breaker from the SENTRON family, built to IEC / EN 60898-1 and IEC / EN 60947-2 / UL1077 standards.

Rated AC operating voltage is 400 V; single- or multi-phase operation goes to 440 V. DC rating is 60 V (max 72 V), with a DC breaking capacity of 15 kA per IEC 60947-2 — useful for DC control circuits or battery-backed supplies. The 5 kA rating under UL 1077 / CSA C22.2 No.235 covers North American acceptance. Temperature range is -40 °C to 75 °C, with a derating curve: max 95% humidity up to 55 °C, tapering to 35% at 75 °C.

Combined terminals top and bottom; supply cord position is unrestricted. Sealable. Mounts in any position via quick-assembly system.

Frequently asked questions

What compliance documentation does Siemens provide for 5SY4116-6-ZW07?

The part is certified to IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 / CSA C22.2 No.235. It is halogen-free and silicon-free. RoHS and REACH declarations are standard from Siemens for the SENTRON series.

Will 5SY4116-6-ZW07 fit a panel designed for 5SY4140-7?

Mechanically yes — both are 18 mm wide, 1-pole SENTRON MCBs with the same mounting footprint and terminal layout. The swap is a straight DIN-rail replacement. The difference is electrical: verify the tripping characteristic and amp rating match the circuit design.

MPN