Skip to main content
Siemens 5SY4116-6CC11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4116-6CC11 SENTRON MCB, 1P B 16 A 10 kA, 400 V

MPN5SY4116-6CC11

Siemens SENTRON 5SY4116-6CC11, 1-pole miniature circuit breaker, B-curve, 16 A rated current, 10 kA breaking capacity at 400 V AC, 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4116-6CC11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY4116-6CC11 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)10 kA
Overvoltage categoryIII
5SY4116-6CC11 — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SY4116-6CC11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY4116-6CC11 is a 1-pole SENTRON miniature circuit breaker (MCB) with a B tripping characteristic, rated at 16 A and 400 V AC, with a 10 kA breaking capacity per EN 60898.

Terminals accept solid or stranded conductors from 0.75 to 35 mm², torqued to 2.5–3.5 N·m. Combined top and bottom terminals simplify daisy-chaining busbars.

Rated 16 A at 400 V AC, B-curve — the breaker holds 16 A continuously and trips magnetically between 48 and 80 A. Energy limiting class 3 keeps let-through energy low, reducing stress on downstream components. Maximum DC voltage is 72 V — usable for DC auxiliary circuits within that limit, but not for 125 V DC rails. No neutral pole switching (1P only).

Sealable terminals allow tamper-proofing after commissioning. Designed for railway applications and mechanical engineering / industry. Suitable for any mounting position.

Frequently asked questions

Where can I buy 5SY4116-6CC11 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the depth of 5SY4116-6CC11?

The depth is 76 mm, with an installation depth of 70 mm.

What conductor sizes does 5SY4116-6CC11 accept?

Solid and stranded conductors from 0.75 to 35 mm², torqued to 2.5–3.5 N·m.

Will 5SY4116-6CC11 drop into a panel specified for 5SY3132-6 without rewiring?

Both are 1-pole SENTRON MCBs on the same DIN-rail footprint (18 mm width), so mechanical fit is identical. The 5SY4116-6CC11 is a 16 A B-curve; the 5SY3132-6 is a different rating and curve — verify the load current and tripping characteristic before substitution.

What compliance documentation does Siemens provide for 5SY4116-6CC11?

The MCB carries EN 60898 certification for breaking capacity. The halogen-free and silicon-free construction supports RoHS/REACH compliance typically, but specific declarations should be requested at order time.

MPN