Rated breaking capacity is 10 kA at 400 VAC per EN 60898, and 5 kA at 440 VAC per UL 1077 / CSA C22.2 No.235. Mounting position is unrestricted, and the IP20 finger-safe enclosure (with conductors connected) suits enclosed panel use — not outdoor or washdown locations.
Integration notes
The quick-assembly fastening method means the breaker clips onto the DIN rail without tools; the combined terminals accept both busbar and conductor connections on the same screw clamp. Operating temperature range from -40 °C to +75 °C covers most industrial environments, but note the humidity derating: max 95% RH at 55 °C, dropping to 35% at 75 °C. If the panel sees sustained high-humidity and high-temperature conditions, factor that into the breaker's thermal performance. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — sufficient for most machine-mounted panels.