SENTRON 5SY4123-7 — 1-pole C-curve MCB, 3.5 A
Breaking capacity is 10 kA per IEC/EN 60898-1 for domestic-type coordination, and 35 kA per IEC 60947-2 / UL1077 for industrial panel applications — the higher figure matters when the prospective fault current at the panel exceeds 10 kA, which is common in transformer-fed switchgear.
At 35 °C ambient the breaker carries its full 3.5 A; at 50 °C it derates to 3.06 A, and at 60 °C to 2.81 A.