Skip to main content
Siemens 5SY4132-5 — 1-Pole MCB (DIN Rail)

Siemens 5SY4132-5 SENTRON MCB, 1P, Characteristic A, 10 kA I

MPN5SY4132-5
Active

Siemens SENTRON 5SY4132-5, 1-pole miniature circuit breaker, characteristic A, 10 kA (IEC/EN 60898-1), 20 kA (IEC 60947-2), 72 VDC max, IP20, 18 mm width.

$67.46Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4132-5 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4132-5 — Electrical & Protection
ParameterValue
Tripping characteristic classA
Overvoltage categoryIII
5SY4132-5 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4132-5 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY4132-5 — SENTRON 1-pole MCB, Characteristic A

Breaking capacity is rated at 10 kA per IEC/EN 60898-1 and 20 kA per IEC 60947-2 at 400 V AC, with a DC rating of 15 kA at 60 V per IEC 60947-2 and 5 kA per UL 1077. That dual-standard rating means the same unit can serve both IEC and UL-classified panels — the 20 kA figure under 60947-2 gives headroom for high-fault industrial environments where a standard 10 kA MCB might not coordinate. Rated operational voltage is 400 V AC (440 V max single- or multi-phase) and 72 V DC maximum.

The sealable design allows lockout/tagout compliance for isolation procedures.

Rated for ambient temperatures from -40 °C to 75 °C, with humidity derating: 95% RH up to 55 °C, 55% RH up to 70 °C, 35% RH up to 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235.

Frequently asked questions

What is the breaking capacity of the 5SY4132-5?

The 5SY4132-5 is rated 10 kA per IEC/EN 60898-1, 20 kA per IEC 60947-2 at 400 V AC, 15 kA at 60 V DC per IEC 60947-2, and 5 kA per UL 1077.

Where can I buy the 5SY4132-5?

The 5SY4132-5 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the tripping characteristic of the 5SY4132-5?

The 5SY4132-5 uses characteristic A, meaning the magnetic trip operates at 2 to 3 times rated current — suited for protecting semiconductor circuits or long cable runs where fast clearing is required.

What compliance documentation does Siemens provide for the 5SY4132-5?

The 5SY4132-5 carries approvals per IEC/EN 60898-1, IEC/EN 60947-2, UL 1077, and CSA C22.2 No. 235. It is halogen-free and silicon-free.

MPN
5SY4132-5