Siemens 5SY4132-5 — SENTRON 1-pole MCB, Characteristic A
Breaking capacity is rated at 10 kA per IEC/EN 60898-1 and 20 kA per IEC 60947-2 at 400 V AC, with a DC rating of 15 kA at 60 V per IEC 60947-2 and 5 kA per UL 1077. That dual-standard rating means the same unit can serve both IEC and UL-classified panels — the 20 kA figure under 60947-2 gives headroom for high-fault industrial environments where a standard 10 kA MCB might not coordinate. Rated operational voltage is 400 V AC (440 V max single- or multi-phase) and 72 V DC maximum.
The sealable design allows lockout/tagout compliance for isolation procedures.
Rated for ambient temperatures from -40 °C to 75 °C, with humidity derating: 95% RH up to 55 °C, 55% RH up to 70 °C, 35% RH up to 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235.