The higher IEC figure applies when the breaker is used as a distribution circuit breaker in an industrial panel with a defined upstream impedance — the 10 kA EN rating is the standard for domestic/commercial final circuits.
Mounting position is unrestricted — horizontal, vertical, or flat — which helps when laying out a dense panel.
Rated for ambient temperatures from -40 °C to 75 °C, with a derating curve above 35 °C: at 40 °C it carries 30.46 A, at 50 °C it carries 28.86 A, and at 60 °C it carries 27.14 A. IP20 with connected conductors — standard for a DIN-rail MCB inside a closed panel.
Application context
The product is designated for railway applications and mechanical engineering/industry. Touch protection is integrated on the terminals.