Siemens 5SY4132-7CV — 1-Pole MCB (DIN Rail)

5SY4132-7CV Siemens MCB, 32 A, C-curve, 15 kA IEC 60947-2

MPN5SY4132-7CV

Siemens 5SY4132-7CV, 1-pole miniature circuit breaker, 32 A rated, C tripping characteristic, 15 kA breaking capacity per IEC 60947-2, 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4132-7CV — Identification
ParameterValue
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4132-7CV — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY4132-7CV — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4132-7CV — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY4132-7CV — 32 A MCB, C-curve, 15 kA

The Siemens 5SY4132-7CV is a 1-pole miniature circuit breaker rated 32 A at AC with a C tripping characteristic and a breaking capacity of 15 kA per IEC 60947-2. Rated current is 32 A at 35 °C ambient, but the breaker derates as the panel warms: 28.45 A at 40 °C, 26.5 A at 45 °C, 24.4 A at 50 °C, and 22.11 A at 55 °C. If your panel runs hot, size the load to the derated value at your actual ambient — the 32 A nameplate is only good at 35 °C. Snaps onto DIN rail (18 mm width, 1 modular unit) and mounts in any position. IP20 with conductors connected — standard for enclosed distribution boards.

Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz. That covers most industrial machinery environments without needing additional damping.

Frequently asked questions

What is the breaking capacity of the Siemens 5SY4132-7CV MCB?

Engineers must confirm 15 kA at IEC 60947-2 before specifying it on a panel.

Is the 5SY4132-7CV suitable for VFD input protection?

C-trip 32A inrush tolerance versus rectifier/DC-bus charging must be justified per drive family.

What auxiliary blocks and accessories are compatible with the 5SY4132-7CV?

Panel builders need exact Siemens 5SY4 accessory part numbers for wiring and signaling.

What are the terminal torque and wire-gauge ratings for the 5SY4132-7CV?

Wiremen need datasheet torque and Cu gauge values to comply with installation specs.

Where can I buy a single Siemens 5SY4132-7CV with datasheet traceability?

Hobbyists and brokers need a low-MOQ, traceable source to avoid counterfeits on allocated SKUs.

What is the lifecycle status and form-fit-function alternate for the 5SY4132-7CV?

Obsolete/LTB and spares managers need EOL flags and qualified alternates before stocking or replacing.

MPN