Skip to main content
Siemens 5SY4132-7KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY4132-7KK11 SENTRON MCB, 1P C-Curve 32A 10kA

MPN5SY4132-7KK11

Siemens SENTRON 5SY4132-7KK11, 1-pole miniature circuit breaker, C-curve, 32 A rated at 35 °C, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4132-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY4132-7KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SY4132-7KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4132-7KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY4132-7KK11 — 1-Pole C-Curve MCB, 32 A, Railway-Rated

It carries a rated current of 32 A at 35 °C, with derated values at elevated ambient temperatures: 30.46 A at 40 °C, 29.66 A at 45 °C, 28.86 A at 50 °C, 28 A at 55 °C, and 27.14 A at 60 °C. This MCB is explicitly designed for railway applications and mechanical engineering/industry use. The installation depth is 70 mm, with an overall depth of 76 mm. It is rated IP20 with connected conductors, suitable for installation in enclosed panels.

Integration — DIN-Rail Fit, Temperature Derating, and Pollution Class

The 18 mm width (1 MW) snaps onto any standard DIN rail. The mounting position is unrestricted — vertical, horizontal, or inverted all work. The energy limitation class is 3, which limits the let-through energy under fault conditions — relevant for coordinating with downstream equipment.

Compliance & Environmental — Halogen-Free, Silicon-Free, Touch Protection

The 5SY4132-7KK11 is halogen-free and silicon-free, meeting material restrictions common in railway, aerospace, and clean-room environments. It is sealable (can be padlocked in the OFF position for lockout/tagout) and includes touch protection on the terminals. The product is designated per IEC 81346-2 and DIN EN 61346-2 with the function code F (protective device).

Frequently asked questions

What is the depth of 5SY4132-7KK11?

The overall depth is 76 mm, with an installation depth of 70 mm.

What is the width of 5SY4132-7KK11?

The width is 18 mm, which is 1 modular width unit.

MPN
5SY4132-7KK11