It carries a 10 kA interrupting rating per EN 60898 and a 15 kA rating per IEC 60947-2, with a 5 kA rating under UL 1077. Rated operational voltage is 400 VAC (440 VAC multi- or single-phase) and 60 VDC (max 72 VDC). The 18 mm width takes one modular unit on a DIN rail, and the unit is sealable with a quick-assembly fastening system.
The 10 kA (EN 60898) and 15 kA (IEC 60947-2) ratings define the maximum prospective short-circuit current the breaker can safely interrupt; the lower UL 1077 figure (5 kA) applies in North American supplementary protection applications. The 400 VAC / 60 VDC voltage ratings cover most three-phase and DC control circuits. The 18 mm width (one modular unit) is the standard DIN-rail footprint for a 1-pole MCB — critical when filling a crowded panel.
Mounting and integration notes
The quick-assembly fastening system allows snap-on installation without tools. The neutral conductor is not switched (1-pole design). The installation depth is 70 mm, and the overall depth is 76 mm — allow clearance for wiring and enclosure door. The unit occupies one modular width unit (18 mm).