It carries a 10 kA interrupting rating per EN 60898 and a 15 kA rating per IEC 60947-2, including DC capability to 15 kA per IEC 60947-2. The breaker occupies 1 modular width unit (18 mm) and mounts in any position.
The 60 A rating holds at 35 °C; above that, derate to 54.42 A at 45 °C, 52.44 A at 50 °C, 50.4 A at 55 °C, and 48.24 A at 60 °C. The breaker is rated for ambient temperatures from -40 °C to 75 °C, with humidity limits of 95% at 55 °C, 55% at 70 °C, and 35% at 75 °C.
Mounting and Installation
Fastens via the quick assembly system, accepts any mounting position, and is sealable. Combined terminals top and bottom. Touch protection is provided. Suitable for mechanical engineering and industry applications.
The part is in a current lifecycle stage. No successor has been announced.