Skip to main content
Siemens 5SY4180-6 — 1-Pole MCB (DIN Rail)

Siemens 5SY4180-6 SENTRON MCB, 1P B-Curve, 10kA IEC

MPN5SY4180-6
Active

Siemens SENTRON 5SY4180-6, 1-pole miniature circuit breaker, B tripping characteristic, 10 kA interrupting capacity per IEC/EN 60898-1, 18 mm width, halogen-free.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4180-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY4180-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY4180-6 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4180-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY4180-6 SENTRON MCB — B-curve, 10 kA, 1-pole

The Siemens 5SY4180-6 is a 1-pole SENTRON miniature circuit breaker (MCB) with a B tripping characteristic, rated to interrupt 10 kA at 400 V AC per IEC/EN 60898-1 and 15 kA at 60 V DC per IEC/EN 60947-2.

The 10 kA breaking capacity at 400 V AC is the figure that governs fault clearance under the EN 60898-1 standard — it means this MCB safely interrupts a short-circuit current up to 10,000 A without welding its contacts or rupturing the case. For DC circuits, the 15 kA rating at 60 V (max 72 V operating) covers battery-backed control buses and solar combiner boxes. The dual-standard listing (IEC 60898-1 for residential/commercial distribution, IEC 60947-2 for industrial switchgear) gives the 5SY4180-6 a wider compliance envelope than a domestic-only MCB; it is accepted in both a lighting sub-panel and a machine control cabinet. The B-curve avoids nuisance tripping on cable charging currents but still clears a hard fault fast enough to protect downstream wiring.

The 18 mm width (1 modular unit) and 70 mm installation depth leave room for adjacent devices in a crowded enclosure. The halogen-free and silicon-free construction matters in environments where outgassing during a fault could corrode nearby contacts or contaminate clean-room air. Ambient operating range spans -40 °C to 75 °C, with humidity derating above 55 °C (95% RH at 55 °C, 55% at 70 °C, 35% at 75 °C).

Frequently asked questions

What is 5SY4180-6's breaking capacity at DC?

The DC breaking capacity is 15 kA at 60 V per IEC/EN 60947-2, with a maximum operating voltage of 72 V DC.

What compliance documentation does Siemens provide for 5SY4180-6?

The MCB is certified to IEC/EN 60898-1 and IEC/EN 60947-2, and carries UL 1077 / CSA C22.2 No.235 ratings (5 kA at AC). It is halogen-free and silicon-free. RoHS and REACH declarations are standard with the Siemens SENTRON series.

Where can I buy 5SY4180-6 and what is the lead time?

The 5SY4180-6 is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ — no stock count or lead-time figure is published here.

MPN
5SY4180-6