Skip to main content
Siemens 5SY4202-7-ZW08 — 2-Pole MCB (DIN Rail)

Siemens 5SY4202-7-ZW08 SENTRON MCB, 2P C-Curve, 10kA IEC 608

MPN5SY4202-7-ZW08
Active

Siemens SENTRON 5SY4202-7-ZW08, 2-pole miniature circuit breaker, C-curve, 10 kA (IEC 60898) / 35 kA (IEC 60947-2), 400 V AC, 2 MW width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4202-7-ZW08 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4202-7-ZW08 — Electrical
ParameterValue
Number of poles2
5SY4202-7-ZW08 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY4202-7-ZW08 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4202-7-ZW08 — Environmental
ParameterValue
Pollution degree3
5SY4202-7-ZW08 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

Siemens 5SY4202-7-ZW08 — SENTRON 2-Pole MCB, C-Curve

The 2-module-width (36 mm) body snaps onto DIN rail and accepts any mounting position. At 400 V AC (multi-phase) the breaker clears fault currents up to 10 kA under EN 60898, and up to 35 kA under IEC 60947-2 — the higher figure matters when the panel SCCR requirement exceeds 10 kA. For DC circuits, it's rated 15 kA at 60 V (72 V max) per IEC 60947-2.

Panel Fit and Environmental Range

The quick-assembly fastening system clips onto the rail without tools — handy when you're populating a row of breakers. Ambient temperature range spans -40 °C to 75 °C, with humidity derating above 55 °C (95% RH to 55 °C, 55% to 70 °C, 35% to 75 °C).

This breaker carries dual certification: IEC/EN 60898-1 for residential-style MCB duty and IEC/EN 60947-2 for industrial use, plus UL 1077 / CSA C22.2 No.235 for supplementary protection in North America. Halogen-free and silicon-free construction simplifies disposal and avoids contamination in sensitive environments like semiconductor fabs or food processing lines.

Frequently asked questions

How do I get current pricing and availability for 5SY4202-7-ZW08?

Submit an RFQ through this listing. We source the part to order and confirm price and availability at quote time.

What is the breaking capacity of this MCB under different standards?

10 kA per IEC 60898-1 at 400 V AC, 35 kA per IEC 60947-2 at 400 V AC, 15 kA per IEC 60947-2 at 60 V DC, and 5 kA per UL 1077 at 440 V AC.

What compliance documentation does Siemens provide for 5SY4202-7-ZW08?

The breaker is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No.235. It's halogen-free and silicon-free, which supports RoHS/REACH compliance.

MPN
5SY4202-7-ZW08