Skip to main content
Siemens 5SY4202-8CC11 — 2-Pole MCB (DIN Rail)

Siemens SENTRON 5SY4202-8CC11 MCB, 2-pole D 2A, 400V 10kA

MPN5SY4202-8CC11

Siemens SENTRON 5SY4202-8CC11, miniature circuit breaker, 2-pole, D tripping characteristic, 2 A rated current, 400 V AC, 10 kA breaking capacity per EN 60898, designed for railway applications.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4202-8CC11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4202-8CC11 — Electrical
ParameterValue
Number of poles2
5SY4202-8CC11 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY4202-8CC11 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4202-8CC11 — Environmental
ParameterValue
Pollution degree3
5SY4202-8CC11 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA
With single-phase operation at AC rated value440 V

Product details

The D tripping characteristic (10–20× In magnetic trip) is the key differentiator here. Compared to a B-curve (3–5× In) or C-curve (5–10× In) MCB, the D-curve tolerates the brief, high starting currents of transformers, DC power supplies, and solenoid valves without nuisance tripping. For a 2 A rated breaker, the magnetic trip threshold sits between 20 A and 40 A — that is the window where a short-circuit or heavy overload will clear, but a normal motor start will pass. EN 60898 certifies the breaker for overcurrent protection in household and similar installations; the railway-design variant (5SY4202-8CC11) adds vibration resistance per IEC 60068-2-6 (±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz) and a wider operating temperature range of -40 °C to 75 °C, which are not found on standard commercial MCBs.

Frequently asked questions

Who supplies 5SY4202-8CC11 and how is it quoted for volume purchases?

The part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time; volume pricing is handled per inquiry.

Will 5SY4202-8CC11 drop into a panel specified around 5SY4101-7CV without rewiring?

Both are 2-pole SENTRON MCBs on the same DIN-rail footprint (36 mm width, 2 MW), so the mechanical fit is identical. The difference is the tripping characteristic: 5SY4202-8CC11 is a D-curve (2 A), while 5SY4101-7CV is a different curve and rating. Verify the load's inrush profile and the required breaking capacity before swapping — the D-curve tolerates higher inrush than a B or C curve, which may or may not match the original design intent.

What compliance documentation does this brand provide for 5SY4202-8CC11?

The manufacturer provides RoHS and REACH declarations on request. The EN 60898 certification covers the 10 kA breaking capacity at 400 V AC. The railway-design variant includes documented vibration resistance per IEC 60068-2-6 and a -40 °C to 75 °C operating temperature range.

MPN