MCB for railway and industrial panels
Designed specifically for railway applications, it also suits general mechanical engineering and industry use.
B-curve means magnetic trip between 3 and 5 times In — 18 to 30 A for this 6 A unit. The 35 kA breaking capacity under IEC 60947-2 is the rating that matters for industrial coordination studies; the 10 kA EN 60898 figure is the domestic/commercial limit. At 40 °C ambient the continuous current derates to 5.63 A; at 60 °C it drops to 4.82 A — factor that into your load schedule if the panel runs hot.