Siemens 5SY4206-6KK11 SENTRON MCB, 2P B-6A, 10kA/35kA

MPN5SY4206-6KK11

Siemens SENTRON 5SY4206-6KK11 miniature circuit breaker, 2-pole, B characteristic, 6 A rated, breaking capacity 10 kA per EN 60898 and 35 kA per IEC 60947-2, railway design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4206-6KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4206-6KK11 — Electrical
ParameterValue
Number of poles2
5SY4206-6KK11 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY4206-6KK11 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4206-6KK11 — Environmental
ParameterValue
Pollution degree3
5SY4206-6KK11 — Specifications
ParameterValue
Energy Limitation Class3

Product details

MCB for railway and industrial panels

Designed specifically for railway applications, it also suits general mechanical engineering and industry use.

B-curve means magnetic trip between 3 and 5 times In — 18 to 30 A for this 6 A unit. The 35 kA breaking capacity under IEC 60947-2 is the rating that matters for industrial coordination studies; the 10 kA EN 60898 figure is the domestic/commercial limit. At 40 °C ambient the continuous current derates to 5.63 A; at 60 °C it drops to 4.82 A — factor that into your load schedule if the panel runs hot.

Frequently asked questions

Where can I buy 5SY4206-6KK11 and how do I get a price?

This part is sourced and quoted to order against an RFQ through our independent distribution channel. Submit an RFQ for current pricing and availability — no stock or price figures are published here.

What is the breaking capacity of 5SY4206-6KK11?

10 kA per EN 60898 and 35 kA per IEC 60947-2. The IEC 60947-2 figure is the one used for industrial coordination studies.

Will 5SY4206-6KK11 drop into a panel specified around 5SY7210-7CC?