Siemens 5SY4206-8CC SENTRON MCB, 2-Pole, 6 A, D Curve, 10 kA

MPN5SY4206-8CC

Siemens SENTRON 5SY4206-8CC, 2-pole miniature circuit breaker, 6 A rated current, D tripping characteristic, 10 kA breaking capacity per EN 60898, AC 50/60 Hz, 440 V max.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4206-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4206-8CC — Electrical
ParameterValue
Number of poles2
5SY4206-8CC — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY4206-8CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4206-8CC — Environmental
ParameterValue
Pollution degree3

Product details

The Siemens SENTRON 5SY4206-8CC is a 2-pole miniature circuit breaker (MCB) rated 6 A at 35 °C with a D tripping characteristic, meaning it's built for loads with high inrush currents — think motor starters, small transformers, or lighting ballasts where the start-up spike would nuisance-trip a B or C curve. The D curve holds through a short-duration surge before opening on sustained overload. Its 10 kA breaking capacity per EN 60898 means it can safely interrupt a fault current up to that level at 440 V AC, which covers most industrial panel secondary circuits. Rated current derates with ambient temperature: 5.51 A at 40 °C, 5.25 A at 45 °C, 4.97 A at 50 °C, and 4.69 A at 55 °C. If your panel runs hot, size up accordingly.

Snaps onto a DIN rail via the quick assembly system — 2 modular width units (36 mm wide), 76 mm deep, 90 mm tall. Mounting position any, supply cord position any — no orientation restrictions.

Frequently asked questions

Where can I buy 5SY4206-8CC and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is 5SY4206-8CC's listed depth?

The listed depth is 76 mm, with an installation depth of 70 mm.

What is 5SY4206-8CC's listed width?

The listed width is 36 mm, which corresponds to 2 modular width units on a DIN rail.

Will 5SY4206-8CC drop into a panel specified around 5SY7210-7CC without rewiring?

The 5SY7210-7CC is a 1-pole unit; the 5SY4206-8CC is 2-pole. They share the same 36 mm width per pole, but the pole count difference means the panel layout and wiring must accommodate the extra pole. No direct drop-in without rewiring.

What compliance documentation does this brand provide for 5SY4206-8CC?

The manufacturer's standard compliance documentation (RoHS, REACH, UL, IEC) applies to the SENTRON series. Specific declarations are available from the manufacturer or distributor upon request.