The quick-assembly mounting system and any-position mounting orientation simplify panel layout — no derating needed for horizontal or inverted fit. Terminal capacity accepts solid or stranded conductors from 0.75 to 35 mm², with a tightening torque of 2.5 to 3.5 N·m.
D-curve and breaking capacity
The D tripping characteristic means the magnetic trip operates at 10 to 20 times the rated current (60 to 120 A for this 6 A unit), making it suitable for loads with high inrush currents — typically motor circuits, transformers, or solenoid banks where a B- or C-curve would nuisance-trip on startup. Overvoltage category III covers fixed-installation distribution boards. The part is also rated for DC circuits up to 72 V, which is useful for control-voltage taps in the same panel.
Humidity tolerance is specified: max 95% at 55 °C, derating to 55% at 70 °C and 35% at 75 °C. The design conforms to EN 60898 for breaking capacity and carries the F designation per DIN EN 61346-2 and DIN EN 81346-2 for circuit-function identification.