It also carries a 15 kA DC rating per IEC 60947-2, so it can handle DC control circuits up to 60 V (72 V max) — common in 48 V or 60 V DC bus systems on conveyor or crusher controls.
Width is 36 mm (2 MW). Depth is 76 mm (70 mm installation depth), height 90 mm. IP20 rating applies with connected conductors — fine inside a locked panel; not for washdown zones. Sealable design lets you lock the toggle position with a padlock hasp, which is useful for lockout/tagout on a maintenance circuit. Halogen-free and silicon-free construction reduces toxic smoke and silicone outgassing in enclosed spaces.
Environmental limits and derating
That covers everything from a frozen winter startup in a Canadian mine to the heat soak next to a crusher drive. Humidity derating is specified: max 95% RH up to 55 °C, tapering to 55% at 70 °C and 35% at 75 °C. If your panel sees sustained high humidity at elevated temperatures, you'll need to account for the reduced moisture tolerance at the top end.