Siemens 5SY4210-7 — 2-Pole MCB (DIN Rail)

Siemens 5SY4210-7 SENTRON MCB, 2P C-Curve, 10kA/20kA

MPN5SY4210-7
Active

Siemens SENTRON 5SY4210-7, 2-pole miniature circuit breaker, C characteristic, 10 kA (EN 60898-1) / 20 kA (IEC 60947-2), 400 V AC, 60 V DC, 2 MW units.

$19.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4210-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4210-7 — Electrical
ParameterValue
Number of poles2
5SY4210-7 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY4210-7 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4210-7 — Environmental
ParameterValue
Pollution degree3
5SY4210-7 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

The DC rating of 15 kA at 60 V (72 V max) extends its use into DC auxiliary circuits, control power supplies, and battery-backed loads — a single part number for mixed AC/DC panels. The quick-assembly fastening method and any-position mounting simplify panel layout — no orientation constraints when you're packing breakers into a tight gland plate.

Rated under IEC / EN 60898-1 for domestic-style installation and IEC / EN 60947-2 for industrial application, plus UL 1077 recognition for North American supplementary protection. The pollution degree 3 rating and overvoltage category III mean it's designed for fixed installations inside a panel, not for handheld or outdoor use.

Integration notes

Combined terminal at both top and bottom accepts supply from any direction — no need to flip the breaker for top-feed vs bottom-feed panels. Neutral conductor is not switched (2-pole without switched neutral), so this breaker protects two phase conductors only; a separate neutral bar is required downstream. Ambient derating applies above 55 °C: max 95% humidity at 55 °C, dropping to 55% at 70 °C and 35% at 75 °C. If the breaker sits near a heat source (transformer, drive heatsink), factor that into the load calculation — the thermal-magnetic trip element responds to both current and ambient temperature.

Frequently asked questions

Where can I buy 5SY4210-7 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key breaking capacity ratings for 5SY4210-7?

10 kA per EN 60898-1, 20 kA per IEC 60947-2 at 400 V AC, and 15 kA per IEC 60947-2 at 60 V DC. For UL 1077 applications the rating is 5 kA.

What compliance documentation does Siemens provide for 5SY4210-7?

The breaker carries IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 certifications. Halogen-free and silicon-free construction is declared. RoHS and REACH compliance documentation is available from Siemens upon request.

MPN