Skip to main content
Siemens 5SY4210-7CC

Siemens 5SY4210-7CC SENTRON MCB, 2P C-Curve 10A, 10kA

MPN 5SY4210-7CC

Siemens SENTRON 5SY4210-7CC, miniature circuit breaker, 2-pole, C-curve, 10 A, 10 kA breaking capacity per EN 60898, 2 MW.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4210-7CC specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

Siemens 5SY4210-7CC SENTRON MCB — 2-Pole, C-Curve, 10 A

Thermal derating and operating envelope

Rated 10 A at 35 °C ambient, the 5SY4210-7CC derates to 9.19 A at 40 °C, 8.75 A at 45 °C, 8.29 A at 50 °C, and 7.81 A at 55 °C. In a sealed, uncooled enclosure near other heat sources, size the continuous load against the 40 °C or 45 °C column — not the 35 °C nominal. Ambient humidity influence is specified: max 95% RH up to 55 °C, tapering to 55% at 70 °C and 35% at 75 °C.

Halogen-free and silicon-free construction, sealable. Neutral conductor is not switched (2-pole, both phases switched). Suitability for mechanical engineering and industry per the manufacturer designation.

MPN