Thermal derating and ambient conditions
Rated current holds at 10 A up to 35 °C. Above that, derate linearly: 9.19 A at 40 °C, 8.75 A at 45 °C, 8.29 A at 50 °C, 7.81 A at 55 °C, and 7.29 A at 60 °C. In a sealed panel near other heat sources, the 40 °C column is the realistic design limit. Ambient humidity tolerance is 95% up to 55 °C, dropping to 35% at the 75 °C max.