Skip to main content
Siemens 5SY4213-8CC — 2-Pole MCB (DIN Rail)

Siemens 5SY4213-8CC SENTRON MCB, 2P D 13A 10kA

MPN5SY4213-8CC

Siemens SENTRON 5SY4213-8CC, miniature circuit breaker, 2-pole, D-curve 13 A, 10 kA per EN 60898, 400 V AC, 2 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4213-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4213-8CC — Electrical
ParameterValue
Number of poles2
5SY4213-8CC — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY4213-8CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4213-8CC — Environmental
ParameterValue
Pollution degree3
5SY4213-8CC — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA
With single-phase operation at AC rated value440 V

Product details

D-curve 13 A — motor and transformer branch protection

Breaking capacity hits 10 kA at 400 V AC per EN 60898, and 5 kA per UL 1077 / CSA C22.2 No.235 — enough for most industrial panel sub-feeders where fault current stays under those thresholds. Rated operating voltage is 400 V AC (440 V max multi- or single-phase), with a DC rating of 72 V max — so it's a pure AC branch breaker; don't spec it for a DC bus.

Thermal and environmental limits

Relative humidity tolerance is 95% at 55 °C, derating to 35% at 75 °C — fine for most indoor industrial environments, but not rated for condensing atmospheres. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — survives normal machine vibration; no special dampening needed in a standard control cabinet.

Siemens designates this breaker for mechanical engineering and industry applications — it's the go-to D-curve 13 A 2P for OEM panel builders and machine builders.

Frequently asked questions

Can the 5SY4213-8CC be used on a DC circuit?

Only up to 72 V DC maximum. This is primarily an AC-rated breaker; for higher DC voltages you'd need a DC-rated series like the Siemens 5SY7.

What is the width of the 5SY4213-8CC?

36 mm, which is 2 modular width units on a standard DIN rail. Depth is 76 mm, installation depth 70 mm.

Does the 5SY4213-8CC accept auxiliary contacts or shunt trips?

Yes, supplementary devices can be installed. The breaker has combined terminals top and bottom and is designed to accept Siemens 5SY-series add-on modules for remote signaling or undervoltage release.

MPN
5SY4213-8CC