Skip to main content
Siemens 5SY4215-7 — 2-Pole MCB (DIN Rail)

Siemens 5SY4215-7 SENTRON MCB, 2P C 1.6 A, 10/35 kA

MPN5SY4215-7
Active

Siemens SENTRON 5SY4215-7, 2-pole miniature circuit breaker, C-curve, 1.6 A rated, 10 kA (EN 60898) / 35 kA (IEC 60947-2) breaking capacity, 2 modular width units.

$33.02Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4215-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4215-7 — Electrical
ParameterValue
Number of poles2
5SY4215-7 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY4215-7 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4215-7 — Environmental
ParameterValue
Pollution degree3
5SY4215-7 — Specifications
ParameterValue
Energy Limitation Class3

Product details

It carries a 10 kA breaking capacity per EN 60898 and a 35 kA rating per IEC 60947-2, giving it selectivity headroom for industrial panel feeders where the higher IEC 60947-2 figure governs the SCCR coordination study.

Mounting position is unrestricted, and the combined top/bottom terminals accept wiring from either direction.

Rated current derates with ambient temperature: 1.6 A at 35 °C, 1.52 A at 40 °C, 1.48 A at 45 °C, 1.44 A at 50 °C, 1.4 A at 55 °C, and 1.36 A at 60 °C. Humidity limits apply: max 95% up to 55 °C, then derated to 55% at 70 °C and 35% at 75 °C. Halogen-free and silicon-free construction. Sealable for lockout/tagout compliance. Energy limitation class 3. Complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL1077.

Frequently asked questions

What is the breaking capacity of 5SY4215-7?

10 kA per EN 60898 and 35 kA per IEC 60947-2. The higher IEC figure is the one to use for industrial SCCR coordination.

What compliance documentation does Siemens provide for 5SY4215-7?

The breaker is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL1077. It is halogen-free and silicon-free.

Where can I buy 5SY4215-7?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
5SY4215-7