Skip to main content
Siemens 5SY4220-7KK11 — 2-Pole MCB (DIN Rail)

Siemens 5SY4220-7KK11 SENTRON MCB, 2P C20, 10kA/20kA

MPN5SY4220-7KK11

Siemens SENTRON 5SY4220-7KK11 miniature circuit breaker, 2-pole, C-curve, 20 A rated, 10 kA per EN 60898 / 20 kA per IEC 60947-2, 2 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4220-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4220-7KK11 — Electrical
ParameterValue
Number of poles2
5SY4220-7KK11 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY4220-7KK11 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4220-7KK11 — Environmental
ParameterValue
Pollution degree3
5SY4220-7KK11 — Specifications
ParameterValue
Energy Limitation Class3

Product details

The 20 A rating is at 35 °C. At 40 °C it derates to 18.78 A, at 50 °C to 17.48 A, and at 60 °C to 16.08 A. The higher IEC figure matters when the breaker is used as a branch-circuit protective device per IEC 60947-2, not just a household-style MCB per EN 60898.

Mounting position any, so it works in vertical or horizontal panel layouts. Sealable for tamper-proofing in metering or rental applications. Touch protection is built in.

Frequently asked questions

Where can I buy 5SY4220-7KK11 and what is the lead time?

Sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

Will 5SY4220-7KK11 drop into a panel designed for 5SY7210-7CC?

Both are 2-pole SENTRON MCBs on the same DIN-rail footprint (2 MW / 36 mm width). The 5SY4220-7KK11 is a C20 (20 A, C-curve); the 5SY7210-7CC is a different rating. If the panel was wired for a 2-pole C-curve MCB at the same or higher ampacity, it will physically fit and terminate the same way. Verify the ampacity matches your load — if the original was a lower rating, the 20 A may be oversized for the wire gauge.

What are the key specifications of 5SY4220-7KK11?

2-pole, C-curve, 20 A rated (derates at elevated ambient), 10 kA breaking capacity per EN 60898 and 20 kA per IEC 60947-2. Dimensions: 36 mm wide, 76 mm deep, 90 mm tall. IP20, overvoltage category III, pollution degree 3. Halogen-free, silicon-free, sealable, with combined terminals.

MPN
5SY4220-7KK11