It carries a 10 kA breaking capacity per EN 60898 and 20 kA per IEC 60947-2, with a DC rating of 15 kA per IEC 60947-2. The unit is halogen-free and silicon-free, making it suitable for environments where material outgassing or particle contamination must be minimized — relevant for semiconductor fab and cleanroom-adjacent panels where low-shedding materials are specified.
The breaker is certified to IEC / EN 60898-1 and IEC / EN 60947-2, plus UL 1077 and CSA C22.2 No. 235. The 5 kA interrupting rating per UL 1077 / CSA is the North American ceiling; the 20 kA per IEC 60947-2 is the higher international ceiling. The part is sealable, which allows tamper-evident locking after commissioning.
Mechanical Integration
Environmental & Material
Humidity influence: max 95% at 55 °C, derating to 35% at 75 °C. Halogen-free and silicon-free construction reduces risk of corrosive outgassing in sealed enclosures — a consideration for semiconductor fab or food-processing panels where material compatibility is audited.