Rated current holds at 25 A up to 35 °C ambient; above that it derates to 23.5 A at 40 °C, 22.72 A at 45 °C, 21.9 A at 50 °C, and 21.05 A at 55 °C. If the panel runs hot, size up or account for the drop.
Mounts in any position, secured via the quick-assembly fastening system. IP20 with conductors connected — standard for enclosed distribution boards. Halogen-free and silicon-free construction matters in environments where outgassing from a fault could contaminate sensitive electronics or process areas — pulp and paper mills, chemical plants, or clean-room adjacent panels.
Ambient temperature range spans -40 °C to 75 °C, with humidity limits: max 95% up to 55 °C, derating to 55% at 70 °C and 35% at 75 °C.