It carries a 10 kA breaking capacity per EN 60898-1 and 20 kA per IEC 60947-2, with a DC rating of 15 kA at 60 V per IEC 60947-2. The D-curve is designed for high inrush loads like motor starters and transformers, where the magnetic trip holds off long enough to avoid nuisance trips on startup.
Physical Fit & Mounting
Depth is 76 mm (70 mm installation depth). The combined top and bottom terminals simplify busbar wiring.
Standards & Environment
Compliant with IEC/EN 60898-1, IEC/EN 60947-2, and UL1077. Pollution degree 3, overvoltage category III. Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz.