Skip to main content
Siemens 5SY4250-8CC — 2-Pole MCB (DIN Rail)

Siemens 5SY4250-8CC SENTRON MCB, 2P D 50A, 10kA, 400V

MPN5SY4250-8CC

Siemens SENTRON 5SY4250-8CC miniature circuit breaker, 2-pole, D tripping characteristic, 50 A rated current, 10 kA breaking capacity at 400 V AC, 2 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4250-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4250-8CC — Electrical
ParameterValue
Number of poles2
5SY4250-8CC — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY4250-8CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4250-8CC — Environmental
ParameterValue
Pollution degree3
5SY4250-8CC — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA
With single-phase operation at AC rated value440 V

Product details

The 10 kA breaking capacity at 400 V (per EN 60898) tells you it can safely interrupt a fault current up to that level without welding contacts or cascading upstream; under UL 1077 and CSA C22.2 No.235 it carries a 5 kA interrupting rating, so verify the available fault current at the panel if the install is in a North American jurisdiction.

The SENTRON series supports installable supplementary devices, so if the application later needs an auxiliary contact, shunt trip, or undervoltage release, the same 2-MW footprint accepts them without re-paneling.

Environmental and mechanical margins

Rated for ambient temperatures from -40 °C to +75 °C, with humidity derating above 55 °C (max 95% RH at 55 °C, 55% at 70 °C, 35% at 75 °C). Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — enough for industrial machinery mounted on a machine frame or conveyor line. Power loss per pole at rated current in hot operating state is 3.8 W, so a 2-pole unit dissipates about 7.6 W total. In a densely packed enclosure, factor that into thermal calculations to avoid derating adjacent devices.

Frequently asked questions

How do I get current pricing and availability for 5SY4250-8CC?

The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Will 5SY4250-8CC drop into a panel specified around 5SY7206-7CC without rewiring?

Both are 2-pole, 2-MW (36 mm wide) SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is identical. The difference is the current rating: 50 A vs 6 A. You cannot swap them without resizing the branch-circuit conductors and verifying the upstream protection — the wiring must match the 50 A rating.

What compliance documentation does Siemens provide for 5SY4250-8CC?

The part carries an EN 60898-rated breaking capacity of 10 kA at 400 V AC and a UL 1077 / CSA C22.2 No.235 rating of 5 kA. It is halogen-free and silicon-free. The manufacturer provides RoHS and REACH declarations as standard for the SENTRON series.

MPN