63 A C-curve MCB for branch-circuit protection
That C-curve means it holds through moderate inrush — typical for motor starters, contactor coils, and transformer primaries — and trips fast on a hard short. Rated frequency is 50/60 Hz. This is a current-production part (lifecycle stage: current).
Temperature derating and mounting
Above that, derate: 60.04 A at 40 °C, 58.46 A at 45 °C, 56.89 A at 50 °C, 55.25 A at 55 °C. Mount in any position on DIN rail (quick-assembly system, 2 modular width units). Depth is 76 mm, width 36 mm, height 90 mm, installation depth 70 mm.
Rated per EN 60898 (10 kA) and UL 1077 / CSA C22.2 No.235 (5 kA). Halogen-free, silicon-free, sealable terminals top and bottom. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Energy limitation class 3. Suitability noted for mechanical engineering and industry applications.