Skip to main content
Siemens 5SY4302-6 — 3-Pole MCB (DIN Rail)

Siemens 5SY4302-6 SENTRON MCB, 3P B-Curve, 10 kA, 400 V

MPN5SY4302-6
Active

Siemens SENTRON 5SY4302-6 miniature circuit breaker, 3-pole, B-curve, 10 kA (EN 60898), 400 V AC, 2 MW units wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4302-6 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4302-6 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-235 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY4302-6 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.5 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY4302-6 — Mechanical
ParameterValue
Modular width units2
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4302-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The Siemens SENTRON 5SY4302-6 is a 3-pole miniature circuit breaker (MCB) with a B tripping curve, rated 10 kA breaking capacity per EN 60898 and 35 kA per IEC 60947-2 at 400 V AC. The 10 kA figure under EN 60898 is the standard household/commercial rating; the 35 kA under IEC 60947-2 gives you the industrial selectivity headroom — a panel designer uses the higher number for coordination studies when the MCB sits downstream of a larger breaker or fuse.

Mounting and integration — DIN-rail fit and spacing

The 5SY4302-6 occupies 2 modular width units (MW) on a DIN rail, with a width of 54 mm, depth 76 mm, and height 90 mm. The quick-assembly fastening method snaps onto the rail without tools. Installation depth is 70 mm, which matters when you're sizing a shallow gland plate or back-panel clearance. IP20 protection with connected conductors — standard for inside a panel; no special sealing needed for dry indoor locations.

Environmental range and suitability for mill or industrial environments

Halogen-free and silicon-free construction is a plus in corrosive atmospheres — no halogens to form acids if the breaker arcs, and no silicone outgassing that could foul contacts in sensitive control circuits. Degree of pollution 3 and overvoltage category III confirm it's rated for the conductive-dust and transient conditions typical of industrial switchgear — not just clean office environments.

Frequently asked questions

What is the breaking capacity of 5SY4302-6?

10 kA per EN 60898 and 35 kA per IEC 60947-2 at 400 V AC, with 15 kA at 60 V DC per IEC 60947-2.

Where can I buy 5SY4302-6?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What standards does 5SY4302-6 comply with?

It complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL1077, and carries the SENTRON brand designation.

MPN