Siemens 5SY4304-6 SENTRON MCB — 3-pole, 4 A, B-curve
The B curve (3–5× In instantaneous trip) is standard for resistive and general-purpose loads: lighting, small heating circuits, control transformers.
Rated 4 A at 35 °C, derated to 3.76 A at 40 °C and 3.22 A at 60 °C — the thermal derating curve is published for panel environments where ambient runs above the 35 °C reference point. If your panel hits 50 °C, the breaker is good for 3.5 A continuous. The 10 kA (EN 60898) and 35 kA (IEC 60947-2) ratings mean the same hardware qualifies for both residential/commercial distribution boards (EN 60898) and industrial switchgear (IEC 60947-2) where prospective short-circuit current can be higher. The 15 kA DC rating per IEC 60947-2 covers DC circuits up to that fault level. IP20 with connected conductors means the terminals are finger-safe only when wired — no washdown rating; this stays in a dry enclosure.
Snap-on DIN rail mounting via the quick-assembly system; 36 mm width (2 MW), 76 mm depth, 90 mm height. Installation depth is 70 mm. Sealable for tamper-proof locking. Halogen-free and silicon-free construction — suitable for clean-room or semiconductor fab environments where outgassing is a concern.