The breaker is sealable — you can lock the toggle in the OFF position for lockout/tagout compliance.
Electrical ratings and selectivity
Rated operational voltage is 400 V AC (440 V max for both single-phase and multi-phase operation). Frequency range 50/60 Hz. DC rating tops out at 72 V — this is primarily an AC breaker; don't spec it for a 110 V DC control bus. The D-curve's magnetic trip threshold (10–20× In) means it won't trip on motor or transformer inrush, but coordination with upstream fuses or an MCCB should still be verified per IEC 60947-2.