Thermal derating and application fit
The 0.5 A rating is at 35 °C ambient. At 40 °C the breaker derates to 0.46 A, at 50 °C to 0.41 A, and at 60 °C to 0.36 A. In a 55 °C railway cabinet, expect 0.39 A continuous capability. If your load draws 0.45 A at 50 °C, this breaker will nuisance-trip — step up to the 5SY4306-7CC11 (1 A) and protect downstream at the actual load current.