Skip to main content
Siemens 5SY4306-6CC — 3-Pole MCB (DIN Rail)

Siemens 5SY4306-6CC SENTRON MCB, 3P B-6A, 10kA

MPN5SY4306-6CC

Siemens SENTRON 5SY4306-6CC miniature circuit breaker, 3-pole, B tripping characteristic, 6 A rated current, 10 kA breaking capacity per EN 60898, 50/60 Hz AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4306-6CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4306-6CC — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY4306-6CC — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.2 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY4306-6CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4306-6CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The Siemens SENTRON 5SY4306-6CC is a 3-pole miniature circuit breaker (MCB) with a B tripping characteristic, rated 6 A at AC and 10 kA breaking capacity per EN 60898. Rated current derates with ambient temperature: 6 A at 35 °C, 5.51 A at 40 °C, 5.25 A at 45 °C, 4.97 A at 50 °C, and 4.69 A at 55 °C. If the panel runs hot — say 50 °C near a drive or transformer — the effective continuous current drops to 4.97 A, so size up one frame if the load is marginal.

Deployment context

Occupies 3 modular width units (54 mm wide, 76 mm deep, 90 mm tall) with a 70 mm installation depth behind the panel face.

The part carries no UL or CSA listing in the evidence; compliance documentation (RoHS, REACH) is standard for Siemens SENTRON series. For a BOM line requiring a UL 489 listed MCB, verify the specific approval against your panel shop's requirements.

Frequently asked questions

Will 5SY4306-6CC drop into a panel that was specified around 5SY4106-7CV without rewiring?

No — the 5SY4106-7CV is single-pole; the 5SY4306-6CC is 3-pole. The footprint, busbar connection, and wiring differ. You would need to rework the distribution board to accept a 3-pole device.

MPN
5SY4306-6CC