Skip to main content
Siemens 5SY4306-8CC — Miniature Circuit Breakers (MCB)

Siemens 5SY4306-8CC SENTRON MCB, 3P D-curve 6A, 10kA

MPN5SY4306-8CC

Siemens SENTRON, miniature circuit breaker, 5SY4306-8CC, 3-pole, D characteristic, 6 A rated current, 10 kA breaking capacity per EN 60898.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SY4306-8CC — Ratings
ParameterValue
Overvoltage categoryIII
5SY4306-8CC — Mechanical
ParameterValue
Width54 mm
Height90 mm
Depth76 mm

Product details

What the ratings mean for your panel

The Siemens 5SY4306-8CC is a SENTRON miniature circuit breaker — 3-pole, D tripping characteristic, rated 6 A at AC. The D curve means it tolerates high inrush currents (typically 10–20× rated), so it's the right choice for motor starters, transformers, or power supplies that pull a heavy surge on energization. The 10 kA breaking capacity per EN 60898 tells you it can safely interrupt a fault current up to that level without welding contacts or cascading upstream — essential for coordination in a distribution board. Under UL 1077 the same part carries a 5 kA interrupting rating, so verify which standard governs your installation.

Mounting and integration

Snaps onto DIN rail via the quick-assembly system; occupies 3 modular width units (54 mm). Depth is 76 mm, installation depth 70 mm — fits standard distribution enclosures without crowding the gland plate. Mounting position is any; IP20 with connected conductors means it's for dry indoor panels only, not washdown areas. Terminal top and bottom are combined (busbar-friendly), and the design is halogen-free and silicon-free — relevant for clean-room or corrosive-environment specs.

Thermal derating and environment

Rated 6 A at 35 °C ambient; at 40 °C it derates to 5.51 A, at 50 °C to 4.97 A, and at 55 °C to 4.69 A. If your panel runs hot (say 50 °C inside), size the load to stay under 5 A per pole. Operating range is -40 °C to 75 °C, with humidity limits: max 95% up to 55 °C, then derating to 35% at 75 °C. Overvoltage category III and pollution degree 3 — suitable for fixed installations downstream of the main distribution board.

Frequently asked questions

What is the breaking capacity of 5SY4306-8CC?

10 kA per EN 60898, and 5 kA per UL 1077 / CSA C22.2 No. 235.

Where can I buy 5SY4306-8CC?

Sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What is the D tripping characteristic used for?

The D curve (10–20× In) handles high inrush loads like motor starters, transformers, and power supplies without nuisance tripping.

MPN
5SY4306-8CC