Siemens 5SY4310-6CC11 — 3-Pole MCB (DIN Rail)

Siemens 5SY4310-6CC11 SENTRON MCB, 3P B-Curve 10A 10kA

MPN5SY4310-6CC11

Siemens SENTRON 5SY4310-6CC11, 3-pole miniature circuit breaker, B-curve, 10 A rated current, 10 kA breaking capacity at 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4310-6CC11 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Suitability for operationMechanical engineering / industry
5SY4310-6CC11 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
5SY4310-6CC11 — Electrical
ParameterValue
Rated current (AC)400 V
Rated voltage (AC, multi-phase)440 V
Rated frequency50/60 Hz
5SY4310-6CC11 — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4310-6CC11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The Siemens SENTRON 5SY4310-6CC11 is a 3-pole miniature circuit breaker (MCB) with a B-curve tripping characteristic, rated at 10 A and 400 V AC. The part is designed for railway applications and mechanical engineering/industry environments, with an IP20 rating (with connected conductors) and a wide ambient temperature range of -40 to +70 °C.

The B-curve trips between 3 and 5 times rated current — so at 30 to 50 A — making it suitable for resistive or general-purpose loads where inrush is modest. The 10 kA breaking capacity at 400 V AC is the standard for most building distribution boards; it confirms the MCB can clear a bolted fault on a 10 kA prospective short-circuit current without rupturing. The 3-pole configuration switches all three phases simultaneously, which is required for three-phase final circuits. Conductor termination accepts solid or stranded wire from 0.75 to 35 mm², with a tightening torque of 2.5 to 3.5 N·m — that range covers standard panel wiring up to 35 mm² for a 10 A circuit.

The MCB mounts via a quick assembly system — the standard DIN-rail clip for SENTRON devices. It occupies 3 width units at 54 mm wide, with a depth of 76 mm and an installation depth of 70 mm. The sealable design supports lockout/tagout procedures.

Frequently asked questions

Where can I buy 5SY4310-6CC11 and get a price?

The 5SY4310-6CC11 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SY4310-6CC11?

The breaking capacity is 10 kA at 400 V AC per EN 60898, which is the standard rating for final subcircuits in building distribution.

What conductor sizes does 5SY4310-6CC11 accept?

It accepts solid or stranded conductors from 0.75 to 35 mm², with a tightening torque of 2.5 to 3.5 N·m.

What compliance documentation is available for 5SY4310-6CC11?

The MCB is designed to EN 60898 (breaking capacity), carries an IP20 protection class, and is rated for overvoltage category III. It is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations are available from the manufacturer upon request.

MPN
5SY4310-6CC11