Skip to main content
Siemens 5SY4310-8CV — 3-Pole MCB (DIN Rail)

5SY4310-8CV MCB, 3-pole D-curve 10 A, 15 kA IEC, 3 MW

MPN5SY4310-8CV

Siemens 5SY4310-8CV, 3-pole miniature circuit breaker, D tripping characteristic, rated current 10 A at 35 °C, breaking capacity 15 kA per IEC 60947-2, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4310-8CV — Identification
ParameterValue
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4310-8CV — Protection
ParameterValue
Tripping characteristic (curve)D
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY4310-8CV — Electrical
ParameterValue
Rated current (AC)10 A
Rated voltage (AC, multi-phase)440 V
Neutral conductor switchingNo
5SY4310-8CV — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
5SY4310-8CV — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The 5SY4310-8CV is a 3-pole miniature circuit breaker with a D tripping characteristic, rated 10 A at 35 °C and built to IEC / EN 60947-2. At 40 °C the continuous rating derates to 9.27 A, at 50 °C to 8.5 A, and at 55 °C to 8.04 A — the thermal-magnetic trip responds to ambient heat, so a panel running hot needs a bigger breaker or a lower load.

Mounting and integration — DIN-rail fit and wiring

Frequently asked questions

How do I get current pricing and availability for 5SY4310-8CV?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is 5SY4310-8CV's listed depth (76 mm) on this component line?

The depth is 76 mm, with an installation depth of 70 mm. The extra 6 mm is the front projection of the toggle and terminal covers.

What is 5SY4310-8CV's listed width (54 mm) on this component line?

The width is 54 mm, which corresponds to 3 modular width units on a standard DIN rail.

Will 5SY4310-8CV drop into a panel that was specified around 5SY4301-7CV without rewiring?

The 5SY4301-7CV is a 1-pole version; the 5SY4310-8CV is 3-pole. They share the same 54 mm width per pole, but the 3-pole unit occupies 3 MW instead of 1 MW. The footprint is different — it will not drop into a single-pole slot without panel rework.

What compliance documentation does this brand provide for 5SY4310-8CV (RoHS, REACH, UL, IEC)?

The breaker is certified to IEC / EN 60947-2. Halogen-free and silicon-free construction is confirmed. The evidence does not list RoHS, REACH, or UL marks; verify with the manufacturer for those specific declarations.

MPN
5SY4310-8CV