Skip to main content
Siemens 5SY4315-8CC11 — 3-Pole MCB (DIN Rail)

Siemens 5SY4315-8CC11 SENTRON MCB, 1.6 A, D Curve, 3-Pole

MPN5SY4315-8CC11

Siemens SENTRON 5SY4315-8CC11, miniature circuit breaker, 3-pole, D characteristic, rated current 1.6 A, breaking capacity 10 kA per EN 60898, for railway applications.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4315-8CC11 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4315-8CC11 — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY4315-8CC11 — Electrical
ParameterValue
Rated current (AC)1.6 A
Rated voltage (AC, multi-phase)440 V
5SY4315-8CC11 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
5SY4315-8CC11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Rated current is 1.6 A at 35 °C, derated to 1.52 A at 40 °C, 1.48 A at 45 °C, 1.44 A at 50 °C, 1.4 A at 55 °C, and 1.36 A at 60 °C.

Halogen-free and silicon-free construction reduces corrosive outgassing in confined enclosures — relevant for sealed railway junction boxes. Operating temperature range spans -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, 55% up to 70 °C, and 35% at 75 °C. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz, matching the mechanical environment of traction equipment.

Frequently asked questions

How do I get pricing and availability for 5SY4315-8CC11?

This part is sourced and quoted to order through independent distribution. Submit an RFQ to confirm current pricing and availability at quote time.

Will 5SY4315-8CC11 drop into a panel specified around 5SY4301-7CV without rewiring?

No — the 5SY4301-7CV is a single-pole device, while the 5SY4315-8CC11 is 3-pole. The footprint, wiring scheme, and terminal count differ. Panel redesign and re-termination would be required.

What compliance documentation does Siemens provide for 5SY4315-8CC11?

The breaker carries a railway-specific design designation and is halogen-free and silicon-free. Standard Siemens documentation includes the declaration of conformity to EN 60898 and IEC 60947-2, plus material compliance declarations (RoHS, REACH) available through the Siemens Industry Online Support portal.

MPN