Breaking capacity and approvals
Rated breaking capacity hits 10 kA per EN 60898 at 400 V AC, and 5 kA per UL 1077 and CSA C22.2 No.235 — so it's certified for both IEC and North American panel builds. Overvoltage category III means it's rated for fixed-installation distribution boards, not just final circuits. The lifecycle stage is current production.
Mounts via quick-assembly system (DIN rail) in any position, occupying 3 width units (54 mm). Combined terminals top and bottom simplify busbar and outgoing wiring.
Environmental and derating
Rated for -40 °C to 75 °C ambient, with humidity derating: 95% RH up to 55 °C, then 55% RH up to 70 °C, then 35% RH up to 75 °C. Halogen-free and silicon-free construction. Mechanical service life typical 10,000 switching cycles.