Skip to main content
Siemens 5SY4325-8CC11 — 3-Pole MCB (DIN Rail)

Siemens 5SY4325-8CC11 SENTRON MCB, 3P D 25A 10kA 400V

MPN5SY4325-8CC11

Siemens SENTRON miniature circuit breaker, 3-pole, D tripping characteristic, 25 A rated current, 10 kA breaking capacity at 400 V AC, for railway applications.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4325-8CC11 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4325-8CC11 — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY4325-8CC11 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)2.1 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY4325-8CC11 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4325-8CC11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The Siemens 5SY4325-8CC11 is a 3-pole miniature circuit breaker from the SENTRON series, rated 25 A with a D tripping characteristic. It breaks 10 kA at 400 V AC (per EN 60898) — that's enough to handle moderate fault levels in industrial and railway distribution panels without upstream reinforcement. The D curve means the magnetic trip holds off inrush from motor loads and transformers; expect it to tolerate 10–20× rated current briefly before snapping open.

Frequently asked questions

What is 5SY4325-8CC11's depth?

The depth is 76 mm; installation depth is 70 mm.

MPN
5SY4325-8CC11